Customization: | Available |
---|---|
Usage: | Industry |
Certification: | CE |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Main Parameters | ||||||||||
Model | ZCH- 1000 |
ZCH- 1500 |
ZCH- 2000 |
ZCH- 2500 |
ZCH- 3000 |
ZCH- 4000 |
ZCH- 5000 |
ZCH- 6000 |
||
Process Airflow(m3/h) | 1000 | 1500 | 2000 | 2500 | 3000 | 4000 | 5000 | 6000 | ||
Supply Air Parameters | Temperature T=15-25 Degree Celsius, Dew Point TL≤-30 Degree Celsius | |||||||||
Power of Process Fan(kw) | 1.1 | 2.2 | 2.2 | 3.0 | 3.0 | 4.0 | 5.5 | 7.5 | ||
Surplus Pressure of the Unit(Pa) | ≥500 | ≥500 | ≥500 | ≥500 | ≥500 | ≥500 | ≥500 | ≥500 | ||
Power of Regeneration Fan(kw) | 0.25 | 0.75 | 0.75 | 0.75 | 1.1 | 1.1 | 1.5 | 1.5 | ||
Surplus Pressure of Regeneration (Pa) | ≥300 | ≥300 | ≥300 | ≥300 | ≥300 | ≥300 | ≥300 | ≥300 | ||
First Rotor Regeneration | Electric (kw) | 3.0 | 3.6 | 4.5 | 6 | 7.2 | 9 | 10.8 | 12 | |
Steam (Kg/h) | 6 | 8 | 10 | 12 | 15 | 18 | 22 | 24 | ||
Second Rotor Regeneration | Electric (kw) | 6 | 7.2 | 9 | 10.8 | 14.4 | 18 | 21.8 | 24 | |
Steam (Kg/h) | 12 | 15 | 18 | 22 | 30 | 36 | 44 | 48 | ||
Steam Pressure(mPa) | 0.4 | |||||||||
Installed Power(kw) | Electric Mode | 10.43 | 13.87 | 16.61 | 20.75 | 25.9 | 31.3 | 39.8 | 45.2 | |
Steam Mode | 1.43 | 3.11 | 3.11 | 3.95 | 4.3 | 5.3 | 7.2 | 9.2 | ||
Power Supply | 3Phase/380V/50Hz | |||||||||
Cooling Load(kw) | 20 | 24 | 30 | 36 | 45 | 60 | 75 | 90 | ||
Dimension | Length(mm) | 3650 | 4200 | 4500 | 6900 | 6900 | 7200 | 7200 | 7500 | |
Width(mm) | 1000 | 1215 | 1250 | 1315 | 1410 | 1505 | 1600 | 1745 | ||
Height(mm) | 1250 | 1350 | 1420 | 1445 | 1540 | 1635 | 1730 | 1825 | ||
Weight(kg) | 800 | 1000 | 1100 | 1200 | 1500 | 1800 | 2000 | 2200 |